Description

READY TO USE

The CMeX10 is ready to use with no configuration required in the field. The possibility of stacking the CMeX10, enables one CMe2100 to handle multiple M-Bus 2-wire buses isolated from each other. After installation, the CMeX10 shows an indication if the installation was successful.

STANDARD OPEN PROTOCOLS

The standard open protocol design works with any software supporting the M-Bus standard. Its transparent M-Bus dataflow require no manufacture specific protocols. 

FLEXIBLE

The CMeX Series contains modules with various functions to meet a great variety of customer demands. The series contains for example I/O modules and D/A modules to read input signals or control output signals.

COST EFFECTIVE

The modular and expandable design allows the customer to select a suitable level based on price and functionality. The low initial cost and the possibility to add modules to existing installations provide a future proof solution.

Technical data

Mechanics
Casing material
Polyamide
Protection class
IP20
Dimensions
90 x 65 x 36 mm
Weight
100 g
Connection M-Bus
Pin terminal solid wire 0.6-0.8 Ø mm
Mounting
DIN Mounted
Power supply
Screw terminal cable 0.75-2.5 mm², 0.5 Nm tightening torque
Electrical
Nominal Voltage
100-240 VAC
Voltage range
-10 % to +10 % of nominal voltage
Frequency
50/60 Hz
Power consumption (max)
3 W
Power consumption (nom)
1.5 mA x M-Bus slaves + 1 W
Installation category
CAT 3
Environmental
Operating temperature range
-30 to +55 °C
Storage temperature range
-40 to +85 °C
Operating humidity max
80 % RH temperatures up to 31 °C, decreasing linearly to 50 %RH at 40 °C
Pollution
Degree 2
Operating altitude
0-2000 m
Usage
Indoor use only, can be extended with IP67 enclosure for outdoor use
User interface
Green LED
Power
Red LED
Error
Yellow LED
RX
Yellow LED
TX
Push button
Not used
M-Bus
M-Bus standard
EN 13757
M-Bus baud rate
300, 2400 Bit/s
Maximum connected M-Bus meters
32
Maximum cable length
1000 m
Max load capacitance
1.5 uF
Light collision detect
>28 to 500 mA
RS232 to M-Bus
No
Break signal length M-Bus 2-wire and right IR interface
45 ms
Nominal voltage
28 VDC
Maximum idle current
55 mA
IR Interface
Yes
Pass Through
Yes. Maximum of 4 CMeX10 Series products side by side
Compatibility
All M-Bus meters, all ABB meters with IR interface, CMeX Series products
Approvals
EMC
EN 61000-6-2, EN 61000-6-3
Safety
EN 61010-1, CAT 3

Downloads

Product sheet
CMeX10 Series Product sheet CMeX10 Series DIN-Mounted M-Bus extenders product sheet
Manual
CMeX10, CMeX11 Quick manual CMeX10, CMeX11 DIN-Mounted M-Bus master for up to 32/64 slaves quick manual
CMeX10 Series User's manual CMeX10 Series DIN mounted M-Bus extenders user's manual

Knowledge base

No knowledge base downloads found.

About Elvaco

Elvaco is a manufacturer and independent supplier of communication equipment and software for collection, processing and presentation of metering data. We deliver high-performing M-Bus masters and slaves for reading of electricity, district heating, water and any other meter following the M-Bus standard.

Contact

Phone: +46 300 30250
Fax: +46 300 18440
Support: +46 300 434300

Contact Form

Elvaco AB
Teknikgatan 18
434 37 Kungsbacka

Newsletter

Terms of use | Quality policy | Environmental policy | Help

Copyright © 2011 Elvaco AB. All rights reserved. Design bureau Vasadu